IEC 60898-1-2002 电气附件.家用和类似设施用的过电流保护断路器.第1部分:交流操作断路器

百检网 2021-08-02
标准号:IEC 60898-1-2002
中文标准名称:电气附件.家用和类似设施用的过电流保护断路器.第1部分:交流操作断路器
英文标准名称:Electrical accessories - Circuit-breakers for overcurrent protection for household and similar installations - Part 1: Circuit-breakers for a.c. operation
标准类型:K31
发布日期:1999/12/31 12:00:00
实施日期:1999/12/31 12:00:00
中国标准分类号:K31
国际标准分类号:29.120.50
适用范围:This part of IEC 60898 applies, to a.c. air-break circuit-breakers for operation at 50 Hz or 60 Hz, having a rated voltage not exceeding 440 V (between phases), a rated current not exceeding 125 A and a rated short-circuit capacity not exceeding 25 000 A. As far as possible, it is in line with the requirements contained in IEC 60947-2. These circuit-breakers are intended for the protection against overcurrents of wiring installations of buildings and similar applications; they are designed for use by uninstructed people and for not being maintained. They are intended for use in an environment with pollution degree 2. They are suitable for isolation. Circuit-breakers of this standard, with exception of those rated 120 V or 120/240 V (see table 1), are suitable for use in IT systems provided that the requirements of IEC 60364-4-473:1977 + A1:1998 are complied with. This standard also applies to circuit-breakers having more than one rated current, provided that the means for changing from one discrete rating to another is not accessible in normal service and that the rating cannot be changed without the use of a tool. This standard does not apply to - circuit-breakers intended to protect motors; - circuit-breakers, the current setting of which is adjustable by means accessible to the user. For circuit-breakers having a degree of protection higher than IP20 according to IEC 60529, for use in locations where arduous environmental conditions prevail (e.g. excessive humidity, heat or cold or deposition of dust) and in hazardous locations (e.g. where explosions are liable to occur), special constructions may be required. Requirements for circuit-breakers for a.c. and d.c. operation are given in IEC 60898-2. Requirements for circuit-breakers which incorporate residual current tripping devices are to be found in IEC 61009-1, IEC 61009-2-1, and IEC 61009-2-2. A guide for co-ordination under short-circuit conditions between a circuit-breaker and another short-circuit protective device (SCPDs) is given in annex D. NOTE 1 For more severe overvoltage conditions, circuit-breakers complying with other standards (e.g. IEC 60947-2) should be used. NOTE 2 For an environment with a higher pollution degree, enclosures giving the appropriate degree of protection should be used. NOTE 3 Circuit-breakers within the scope of this standard may also be used for protection against electric shock in case of fault, depending on their tripping characteristics and on the characteristics of the installation. The criterion of application for such purposes is dealt with by installation rules. This standard contains all requirements necessary to ensure compliance with the operational characteristics required for these devices by type tests. It also contains the details relative to test requirements and methods of testing necessary to ensure reproducibility of test results. This standard states a) the characteristics of circuit-breakers; b) the conditions with which circuit-breakers shall comply, with reference to: 1) their operation and behaviour in normal service; 2) their operation and behaviour in case of overload; 3) their operation and behaviour in case of short-circuits up to their rated short-circuit capacity; 4) their dielectric properties; c) the tests intended for confirming that these conditions have been met and the methods to be adopted for the tests; d) the data to be marked on the devices; e) the test sequences to be carried out and the number of samples to be submitted for certification purposes (see annex C); f) the co-ordination under short-circuit conditions with another short-circuit protective device (SCPD) associated in the same circuit (see annex D); g) the routine tests to be carried out on each circuit-breaker to reveal unacceptable variations in material or manufacture, likely to affect safety (see annex I).

百检能给您带来哪些改变?

1、检测行业全覆盖,满足不同的检测;

2、实验室全覆盖,就近分配本地化检测;

3、工程师一对一服务,让检测更精准;

4、免费初检,初检不收取检测费用;

5、自助下单 快递免费上门取样;

6、周期短,费用低,服务周到;

7、拥有CMA、CNAS、CAL等权威资质;

8、检测报告权威有效、中国通用;

客户案例展示

  • 上海朗波王服饰有限公司
  • 浙江圣达生物药业股份有限公司
  • 天津市长庆电子科技有限公司
  • 上海纽特丝纺织品有限公司
  • 无锡露米娅纺织有限公司
  • 东方电气风电(凉山)有限公司